Do we need to provide any test log for test DLL013?

Modified on Fri, 7 Aug, 2020 at 1:26 PM

The HART Test System does not currently run an automated test for DLL013.   


For DLL013: In order to satisfy compliance with these tests you simply need to do a “code walk”—carefully go through and review your code manually until you are satisfied that the device will behave properly under the circumstances presented in the tests. When submitting the device, please note in your submission that these tests were performed manually. There are also a few UAL and CAL tests that are not automated. You may use this same method to check them or create your own scripts to test them.


If you develop an automated test for DLL013, you can report the findings as log files with a summary in the Field Device Specification.


If you perform a manual audit of the firmware, please include a summary of the audit in the Field Device Specification. 