SDC625 runs fine on Windows 10.

The problem is the Installer does not install it properly on that Operating System.

At this time users must execute some manual steps to get it functioning.


1)  Generate a batch file in the  C:\HCF\Common  directory. We use the name RegisterThese.bat.  It should have the following lines in it:

hmodemsvr -RegServer

regsvr32  hselect.dll

regsvr32  hutil.dll

2)  Open a command prompt AS ADMINISTRATOR and cd to the C:\HCF\Common  directory and run the batch file you constructed in (1) above. 

You should see a message box open to say registration was successful and when finished, this is what you should see:


If the SDC gives you a .dll error, your Windows 10 installation probably did not include the VS2008 redistributable dlls.

You can obtain them from here:

https://www.microsoft.com/en-us/download/details.aspx?id=29

With those installed, the SDC should work as it did on Windows 7.  Other setup like selecting the correct COM  port is exactly the same as the Windows 7 operation.